incinerator capacity calculation

Test shall be conducted by factory authorized representative of incinerator manufacturer.

 

  1. Demonstrate required weight reduction of specified waste. Waste shall be fed in a single batch to the unit.

After termination of manufacturer’s predicted burning period, inspect and weigh the residue.

 

  1. Emissions testing may be deleted if not required by state or local authorities. List all additional tests

required by state and local emission authorities.

 

  1. Emissions:

 

  1. Test shall be conducted by independent testing organization provided by Contractor which has a minimum of three

years experience in emissions testing and which has been approved by the pollution control authority that has

jurisdiction.

 

  1. Conduct tests during the reduction of waste test specified above.

 

  1. Test methods must comply with EPA Reference Method 5, 40 CFR 60, Appendix B, “Determination of Particulate

Emissions from Stationary Sources”.

 

  1. Demonstrate that incinerator complies with specified emission limits.

 

  1. Sound Levels: Demonstrate conformance to sound level limitation.

 

  1. Report: Furnish complete written report (three copies), which includes test data, calculations, results

compared with requirements, list of personnel, and other pertinent information. Furnish report within three weeks of

test date.