The panel and parts hereof shall have the following characteristics:

 

 

 

 

Finish

 

All metal parts shall receive a treatment taking the prevailing environment conditions into account.

 

 

 

 

The top paint colour shall be the Manufacturer’s standard.

 

 

 

 

Auxiliary Wiring

 

 

 

 

All auxiliary wiring shall be carried out with wires having a minimum cross section area of

1.5 mm2.

 

 

 

 

Wiring is connected to terminals blocks in such a way that there is no more than two wires on each terminal.

 

 

 

 

Current wires from current transformers shall be not less than 6 mm2.

 

 

 

 

All wires shall be marked at each end for identification.

 

 

 

 

All markings shall be carried out in compliance with the corresponding circuit diagrams and wiring lists.

 

 

 

 

Cable Termination

 

 

 

 

Auxiliary wires will be terminated to numbered terminals.

 

 

 

 

Main circuit cables will be bolted to numbered bars.